Station Post Insulator IEC C Series

Station Post Insulator IEC C Series

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

Product Introduction

Each of our 27kV Composite Fuse Cut Body, 10kV Composite Long Rod Insulator, 220kV Composite Station Post Insulator is carefully designed by us, not only with superior quality but also exquisite appearance. The goal of our company is to integrate resources, expand the market, run efficiently and operate in an orderly manner. We will take the scientific concept of development as our guide and vigorously implement the strategy of strengthening the enterprise with talents.

Post Insulators 16kN With Top And Bottom Flange.

Detailed Description

Rated Voltage:

72.5kV

SCL:

16kN

Type:

Station Post

Type Test:

Provide

Material:

Composite, Polymer

Sample Available:

Yes

 

Reasonable Design and Excellent material

 

End Fittings

Core

Sheds and Housing

Materials: Hot dip galvanized cast iron or cast steel

Epoxy & Glass Fiber

HTV Silicone Rubber

Min. thickness of the galvanization: 86μm

Rod Diameter: Φ70mm

Color: Gray,Red

station post insulators

 Technical Data

Rated Voltage
(kV)

Height
(mm)

Dry Arcing Distance
(mm)

Creepage Distance
(mm)

Specified Cantilever Load
(SCL)

Max. Design Cantilever Load
(MDCL)

Max. Design Torsion Load
(MDTol)

Dry Power Frequency Withstand Voltage
(kV)

Lightning Impulse Withstand Voltage
(kV)

72.5

770±1

682mm

1813

16kN

10kN

1.2kN • m

165

325

 

Post Insulators Inspection and Testing

1.1Type Tests

The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.

(i)Verification of the dimensions

(ii)Mechanical failing load

(iii)Thermal-mechanical performance test

(iv)Dry lightning impulse withstand voltage test

(v)Wet Power-frequency withstand voltage test

 

1.2Routine Tests

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

(i)Routine visual inspection

(ii)Routine mechanical test

(iii)Routine electrical test

 

1.3Acceptance Tests

(i)Verification of the dimensions

(ii)Mechanical failing load test

 

 

tes

Marking

Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.

 

Package and Transportation

Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.

Contact now

 

 

 

Our well-equipped facilities and great good quality regulate throughout all stages of manufacturing enables us to guarantee total buyer gratification for Station Post Insulator IEC C Series. Our consistent aim is to provide high-quality products and services to help customers grow. Due to the changing trends in this field, we involve ourselves into products trade with dedicated efforts and managerial excellence.