After years of experience accumulation and technological innovation, our equipment has been at the forefront of the 132kv Post Insulator, Composite Polymer Deadend Insulators, 138kV Composite Line Post Insulator industry. The equipment is not only sold throughout the country, but also exported to more than 20 countries and regions around the world. Favor and praise from users. We are a company that is focused on innovation and growth. Our belief in integrity and honesty is reflected in every aspect of our business operations.
Post Insulators 16kN With Top And Bottom Flange.
Detailed Description
|
Rated Voltage: |
72.5kV |
SCL: |
16kN |
|
Type: |
Station Post |
Type Test: |
Provide |
|
Material: |
Composite, Polymer |
Sample Available: |
Yes |
Reasonable Design and Excellent material
|
End Fittings |
Core |
Sheds and Housing |
|
Materials: Hot dip galvanized cast iron or cast steel |
Epoxy & Glass Fiber |
HTV Silicone Rubber |
|
Min. thickness of the galvanization: 86μm |
Rod Diameter: Φ70mm |
Color: Gray,Red |

Technical Data
|
Rated Voltage |
Height |
Dry Arcing Distance |
Creepage Distance |
Specified Cantilever Load |
Max. Design Cantilever Load |
Max. Design Torsion Load |
Dry Power Frequency Withstand Voltage |
Lightning Impulse Withstand Voltage |
|
72.5 |
770±1 |
682mm |
1813 |
16kN |
10kN |
1.2kN • m |
165 |
325 |
Post Insulators Inspection and Testing
1.1Type Tests
The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.
(i)Verification of the dimensions
(ii)Mechanical failing load
(iii)Thermal-mechanical performance test
(iv)Dry lightning impulse withstand voltage test
(v)Wet Power-frequency withstand voltage test
1.2Routine Tests
The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.
(i)Routine visual inspection
(ii)Routine mechanical test
(iii)Routine electrical test
1.3Acceptance Tests
(i)Verification of the dimensions
(ii)Mechanical failing load test

Marking
Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.
Package and Transportation
Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.
We strive for excellence, services the customers', hopes to be the top cooperation team and dominator business for personnel, suppliers and prospects, realizes benefit share and continual promotion for 130kv Composite Station Post Insulators. Our sales network has successfully spread all over the world, our products are deeply trusted and praised by customers, and the related supporting industry chain is perfect. We keep pace with the times, explore market demand in depth, and continuously invest in research and development of new styles and products that strive for excellence.
Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, ANSI line post insulator, Post Insulator 150 Kv, Composite Long Rod Insulator, Composite Suspension Insulators For Railway, 45kV composite polymer pin insulator, 35kV DS Insulator