22kv IEC Composite Insulator/Station Post Insulator

22kv IEC Composite Insulator/Station Post Insulator

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

Product Introduction

Our company has a strong presence in Composite Tension Insulator For Railway, Composite Suspension insulator for electrified railway, Composite polymer long rod insulator associations and organizations. Our dedication to quality ensures that all of our products meet or exceed industry standards and regulations. Delight our clients by understanding their challenges and proactively delivering real solutions.

Post Insulators 16kN With Top And Bottom Flange.

Detailed Description

Rated Voltage:

72.5kV

SCL:

16kN

Type:

Station Post

Type Test:

Provide

Material:

Composite, Polymer

Sample Available:

Yes

 

Reasonable Design and Excellent material

 

End Fittings

Core

Sheds and Housing

Materials: Hot dip galvanized cast iron or cast steel

Epoxy & Glass Fiber

HTV Silicone Rubber

Min. thickness of the galvanization: 86μm

Rod Diameter: Φ70mm

Color: Gray,Red

station post insulators

 Technical Data

Rated Voltage
(kV)

Height
(mm)

Dry Arcing Distance
(mm)

Creepage Distance
(mm)

Specified Cantilever Load
(SCL)

Max. Design Cantilever Load
(MDCL)

Max. Design Torsion Load
(MDTol)

Dry Power Frequency Withstand Voltage
(kV)

Lightning Impulse Withstand Voltage
(kV)

72.5

770±1

682mm

1813

16kN

10kN

1.2kN • m

165

325

 

Post Insulators Inspection and Testing

1.1Type Tests

The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.

(i)Verification of the dimensions

(ii)Mechanical failing load

(iii)Thermal-mechanical performance test

(iv)Dry lightning impulse withstand voltage test

(v)Wet Power-frequency withstand voltage test

 

1.2Routine Tests

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

(i)Routine visual inspection

(ii)Routine mechanical test

(iii)Routine electrical test

 

1.3Acceptance Tests

(i)Verification of the dimensions

(ii)Mechanical failing load test

 

 

tes

Marking

Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.

 

Package and Transportation

Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.

Contact now

 

 

 

Each individual member from our large performance revenue crew values customers' needs and company communication for 22kv IEC Composite Insulator/Station Post Insulator. We are your next business partner. The company has many skilled technicians, and its strong technical force, strict quality management order, and professional production lines are the guarantee of our pursuit of high quality.

Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, Composite Post Insulators For Railway, Composite Braced Post Insulator, polymer post insulator, Suspension insulator, Silicone rubber insulator, 33kv Polymer Pin Insulator