6kn Porcelain Station Post Insulator

6kn Porcelain Station Post Insulator

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

Product Introduction

We constantly adjust our product structure and develop new HDPE Pin Insulators, Composite Station Post Insulator, Polymeric suspension insulators to meet the changing market demand. We have won the approval of our customers with our fast, efficient and perfect after-sales service in our years of operation. Selling our products causes no risks and brings high returns to your company instead. Our team of experts is dedicated to staying up-to-date with the latest industry trends and best practices to better serve our customers.

Post Insulators 16kN With Top And Bottom Flange.

Detailed Description

Rated Voltage:

72.5kV

SCL:

16kN

Type:

Station Post

Type Test:

Provide

Material:

Composite, Polymer

Sample Available:

Yes

 

Reasonable Design and Excellent material

 

End Fittings

Core

Sheds and Housing

Materials: Hot dip galvanized cast iron or cast steel

Epoxy & Glass Fiber

HTV Silicone Rubber

Min. thickness of the galvanization: 86μm

Rod Diameter: Φ70mm

Color: Gray,Red

station post insulators

 Technical Data

Rated Voltage
(kV)

Height
(mm)

Dry Arcing Distance
(mm)

Creepage Distance
(mm)

Specified Cantilever Load
(SCL)

Max. Design Cantilever Load
(MDCL)

Max. Design Torsion Load
(MDTol)

Dry Power Frequency Withstand Voltage
(kV)

Lightning Impulse Withstand Voltage
(kV)

72.5

770±1

682mm

1813

16kN

10kN

1.2kN • m

165

325

 

Post Insulators Inspection and Testing

1.1Type Tests

The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.

(i)Verification of the dimensions

(ii)Mechanical failing load

(iii)Thermal-mechanical performance test

(iv)Dry lightning impulse withstand voltage test

(v)Wet Power-frequency withstand voltage test

 

1.2Routine Tests

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

(i)Routine visual inspection

(ii)Routine mechanical test

(iii)Routine electrical test

 

1.3Acceptance Tests

(i)Verification of the dimensions

(ii)Mechanical failing load test

 

 

tes

Marking

Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.

 

Package and Transportation

Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.

Contact now

 

 

 

We combine technology and craftsmanship to create the perfect 6kn Porcelain Station Post Insulator upholding the perseverance and pioneering spirit, and integrating rich production experience. All along, our company's market reputation has been recognized by the customers. Finest Rate Forever High-quality in China.

Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, Composite Post Insulators For Railway, 66kV Composite Long Rod Insulator, 10kV Pin Insulators, 10kV Composite Pin Insulator, Polymer suspension insulator, 138kV Composite Stay Insulator

Send Inquiry

whatsapp

teams

E-mail

Inquiry