Our company has been focusing on the research of Composite Deadend Insulator, 38kV Composite Fuse Cut Body, 132kv Post Insulator for several years, has accumulated its own scientific and technological guidance system, formed its own product series with clear specialization characteristics, built a number of customer groups, and has the foundation for enterprise development. Start a new journey, we are willing to work hand in hand with the community to create a better future! Future enterprises must belong to enterprises with technology and quality. Only quality and technology are the foundation for enterprises to survive for a long time.
Post Insulators 16kN With Top And Bottom Flange.
Detailed Description
|
Rated Voltage: |
72.5kV |
SCL: |
16kN |
|
Type: |
Station Post |
Type Test: |
Provide |
|
Material: |
Composite, Polymer |
Sample Available: |
Yes |
Reasonable Design and Excellent material
|
End Fittings |
Core |
Sheds and Housing |
|
Materials: Hot dip galvanized cast iron or cast steel |
Epoxy & Glass Fiber |
HTV Silicone Rubber |
|
Min. thickness of the galvanization: 86μm |
Rod Diameter: Φ70mm |
Color: Gray,Red |

Technical Data
|
Rated Voltage |
Height |
Dry Arcing Distance |
Creepage Distance |
Specified Cantilever Load |
Max. Design Cantilever Load |
Max. Design Torsion Load |
Dry Power Frequency Withstand Voltage |
Lightning Impulse Withstand Voltage |
|
72.5 |
770±1 |
682mm |
1813 |
16kN |
10kN |
1.2kN • m |
165 |
325 |
Post Insulators Inspection and Testing
1.1Type Tests
The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.
(i)Verification of the dimensions
(ii)Mechanical failing load
(iii)Thermal-mechanical performance test
(iv)Dry lightning impulse withstand voltage test
(v)Wet Power-frequency withstand voltage test
1.2Routine Tests
The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.
(i)Routine visual inspection
(ii)Routine mechanical test
(iii)Routine electrical test
1.3Acceptance Tests
(i)Verification of the dimensions
(ii)Mechanical failing load test

Marking
Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.
Package and Transportation
Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.
As one of the best suppliers of ANSI Porcelain Station Post Insulator for Transmission and Substation, we have a significant market share and we are proud to be ahead of the pack in the industry. We will continue to develop and manufacture new products that are more suitable for market needs. In the future, We will integrate industrial resources efficiently and continuously innovate business models with a global perspective.
Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, 115kV Composite Deadend Insulators, Composite Line Post Insulator, 27kV Composite Fuse Cut Body, Composite Braced Line post Insulator, 33kV composite polymer pin insulator, Silicone rubber insulator