Composite Insulator Polymer Silicone Rubber Station Post Insulator

Composite Insulator Polymer Silicone Rubber Station Post Insulator

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

Product Introduction

We pursue professional 69kV Composite Station Post Insulator, Composite Braced Post Insulator, Composite Post insulator for electrified railway , have rich industry experience, serve customers as the purpose, in the design and manufacture of all products reflect the customer's valuable opinions and market applicability. The development of the enterprise should benefit the country, the nation and the people, and benefit the end customers and consumers. All products are manufactured with advanced equipment and strict QC procedures in order to ensure high quality. We believe in partnering with our clients to achieve their goals. Adhering to the business principle of becoming stronger and bigger, we insist on "survival by quality, progress by technology, development by innovation, and reputation by service".

Post Insulators 16kN With Top And Bottom Flange.

Detailed Description

Rated Voltage:

72.5kV

SCL:

16kN

Type:

Station Post

Type Test:

Provide

Material:

Composite, Polymer

Sample Available:

Yes

 

Reasonable Design and Excellent material

 

End Fittings

Core

Sheds and Housing

Materials: Hot dip galvanized cast iron or cast steel

Epoxy & Glass Fiber

HTV Silicone Rubber

Min. thickness of the galvanization: 86μm

Rod Diameter: Φ70mm

Color: Gray,Red

station post insulators

 Technical Data

Rated Voltage
(kV)

Height
(mm)

Dry Arcing Distance
(mm)

Creepage Distance
(mm)

Specified Cantilever Load
(SCL)

Max. Design Cantilever Load
(MDCL)

Max. Design Torsion Load
(MDTol)

Dry Power Frequency Withstand Voltage
(kV)

Lightning Impulse Withstand Voltage
(kV)

72.5

770±1

682mm

1813

16kN

10kN

1.2kN • m

165

325

 

Post Insulators Inspection and Testing

1.1Type Tests

The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.

(i)Verification of the dimensions

(ii)Mechanical failing load

(iii)Thermal-mechanical performance test

(iv)Dry lightning impulse withstand voltage test

(v)Wet Power-frequency withstand voltage test

 

1.2Routine Tests

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

(i)Routine visual inspection

(ii)Routine mechanical test

(iii)Routine electrical test

 

1.3Acceptance Tests

(i)Verification of the dimensions

(ii)Mechanical failing load test

 

 

tes

Marking

Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.

 

Package and Transportation

Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.

Contact now

 

 

 

We are a manufacturer for Composite Insulator Polymer Silicone Rubber Station Post Insulator that you can always trust. Browse our online showroom to see what we can do for you. We sincerely hope that all customers will establish long term and mutually beneficial cooperation with us.

Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, 11kv Polymer Pin Insulator, 220V Composite Long Rod Insulator, Polymer suspension insulator, 138kV Composite Stay Insulator, Spare Parts For Composite Insulators, 138kV Composite Station Post Insulator

Send Inquiry

whatsapp

teams

E-mail

Inquiry