We adhere to the business philosophy of "integrity and professionalism", with innovation as the soul and customer satisfaction as the standard, providing first-class 35kV Composite Post Insulators, Composite Stay Insulator, Composite Braced Post Insulator with reliable performance, leading technology, and excellent service! We are committed to cultivating new models and formats, and accelerating the realization of the goal of building a world-class enterprise. Striving for perfection is of course outstanding. Every product of the company is the dedication of our sincerity and love. At the same time, it also incorporates perfect service.
Improvements in electrode shape
Improvements in electrode shape
The average breakdown field strength of uniform electric field and slightly inhomogeneous electric field gap is much higher than that of extremely inhomogeneous electric field gap. Generally speaking, the more uniform the electric field distribution, the higher the average breakdown field strength. Therefore, the electrode shape can be improved and the electrode curvature radius can be increased to improve the electric field distribution and increase the breakdown voltage of the gap. At the same time, the electrode surface should try to avoid burrs, edges, etc. to eliminate the phenomenon of local enhancement of the electric field. If an extremely non-uniform electric field is unavoidable, a symmetrical electric field (rod-rod type) should be used whenever possible.
Even if the electric field is extremely uneven, in many cases, in order to avoid strong corona discharge under the operating voltage, the electrode curvature radius must be increased.
Figure 2-25 shows some methods of changing the shape of the electrode to adjust the electric field. These methods can be summarized as follows:
(1) Increase the radius of curvature of the electrode: For example, add a spherical shield to the end of the transformer bushing (see Figure 2-25(a)), use expanded diameter wires (the cross-section is the same, the radius is increased, see figure 2-25(b)), etc., use the method of increasing the electrode curvature radius to reduce the surface field strength.
(2) Improve the electrode edge: The electrode edge should be made into an arc, or try to make it as close as possible to an equipotential surface (see Figure 2-25(c)) to eliminate the edge effect.
![8KHO79]7T7`JD]UQ6F0BY6K 8KHO79]7T7`JD]UQ6F0BY6K](/Content/uploads/2023658154/202309111047341fa3c301d9d14beba1b21996f33c01c1.png)
(3) Make the electrode have the best shape; such as adding a metal flat ball to the high-voltage lead through the wall, and the edge of the wall hole is made into a rotating body similar to a vertical chain line (see Figure 2-25(d)), so as to improve its electric field distribution.
Adjusting the electric field and reducing the local excessively high field strength are effective measures to improve the electric strength not only for the gas gap but also for other insulation structures. For different insulation structures, in addition to improving the electrode shape, other methods of adjusting the electric field can also be used.
solid insulating covering
solid insulating covering
In a slightly uneven electric field, covering the surface of the high-field-strength electrode with a solid paper insulating layer can also increase the gap breakdown voltage, and the covering layer has a significant effect on increasing the air gap breakdown voltage, but covering the counter electrode with an insulating layer , to improve the air gap breakdown voltage research needs to be further in-depth.
Products Insulator Factory Direct

Insulator designed mainly for flexural loads (bending) but also tension and compression, thus having combined loading capability. Normally utilized as a single unit can also be a double insulator assembly. Composite materials are most suitable for the application on compact lines and retrofitting due to their flexibility, overloads absorption capacity and reduced weight. We have thousands of pieces line post from 33kV to 362kV worked on lines all over the world, and there is no single accidents happens.
We have our own silicone rubber workshop and lab. Each batch of rubber shall be tested and we have our own formula which makes our insulator tracking and earsion performance stable and good. Below is the key parameter of our rubber.

Our company with strong strength, reasonable price, good service and a number of enterprises to establish a long-term partnership. With high quality products and perfect after-sales service, we have won the consistent reputation of customers all over the country. We sincerely welcome customers from home and abroad to visit, investigate and discuss business cooperation.





Our commission is to serve our buyers and purchasers with most effective good quality and aggressive portable digital goods for Solid-Core Electrical Isolator 11kv Pin Composite 150kv Post Insulator. Many large trading companies import products from us, so we can give you the best price with the same quality if you are interested in us. We work tirelessly to build the status of the industry, and believe that the company will lead the new generation of industry trends with our unique style.
Hot Tags: composite post insulator, China, manufacturers, suppliers, factory, wholesale, for sale, 69kV Composite Station Post Insulator, Spare Parts For Composite Insulators, 138kV Composite Station Post Insulator, 33kv Polymer Pin Insulator, 132kv Post Insulator, 27kV Composite Fuse Cut Body