Tr Solid-Core Station Post Ceramic Insulator

Tr Solid-Core Station Post Ceramic Insulator

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

Product Introduction

We wish to introduce ourselves to you as a private company dealing exclusively in 35kV DS Insulator, Composite Station Post Insulator, Composite Tension Insulator . Our company has become an enterprise with good influence by establishing a win-win independent operation mode. Internally, we are committed to improving the service quality. Externally, we build an open platform. Our company is committed to upholding the highest standards of ethics, honesty, and integrity in all our business practices. We enjoy a high position among consumers and have established long-term cooperative relationships with many companies. Competition is not only the objective law of market economy, but also the internal demand of enterprise development.

Post Insulators 16kN With Top And Bottom Flange.

Detailed Description

Rated Voltage:

72.5kV

SCL:

16kN

Type:

Station Post

Type Test:

Provide

Material:

Composite, Polymer

Sample Available:

Yes

 

Reasonable Design and Excellent material

 

End Fittings

Core

Sheds and Housing

Materials: Hot dip galvanized cast iron or cast steel

Epoxy & Glass Fiber

HTV Silicone Rubber

Min. thickness of the galvanization: 86μm

Rod Diameter: Φ70mm

Color: Gray,Red

station post insulators

 Technical Data

Rated Voltage
(kV)

Height
(mm)

Dry Arcing Distance
(mm)

Creepage Distance
(mm)

Specified Cantilever Load
(SCL)

Max. Design Cantilever Load
(MDCL)

Max. Design Torsion Load
(MDTol)

Dry Power Frequency Withstand Voltage
(kV)

Lightning Impulse Withstand Voltage
(kV)

72.5

770±1

682mm

1813

16kN

10kN

1.2kN • m

165

325

 

Post Insulators Inspection and Testing

1.1Type Tests

The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.

(i)Verification of the dimensions

(ii)Mechanical failing load

(iii)Thermal-mechanical performance test

(iv)Dry lightning impulse withstand voltage test

(v)Wet Power-frequency withstand voltage test

 

1.2Routine Tests

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

(i)Routine visual inspection

(ii)Routine mechanical test

(iii)Routine electrical test

 

1.3Acceptance Tests

(i)Verification of the dimensions

(ii)Mechanical failing load test

 

 

tes

Marking

Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.

 

Package and Transportation

Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.

Contact now

 

 

 

To create much more benefit for Tr Solid-Core Station Post Ceramic Insulator. We always insist on co-innovating products, and jointly developing markets with various brand enterprises. Our company is rooted in the local area looking internationally, and constantly improving our strength with cutting-edge technology.

Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, 25kV Composite Deadend insulators, Composite Station Post Insulator, Composite polymer long rod insulator, 330kV station post insulator, Suspension insulator, Polymer Station Post Insulators

Send Inquiry

whatsapp

teams

E-mail

Inquiry