We have a wide range of market development, mature market operation, and the excellent quality of our 220V Composite Long Rod Insulator, 138kV Composite Stay Insulator, 33kv Post Insulator Drawing has received a warm response from the market! Our products are rigorously tested to ensure compliance with all international regulations. We are committed to maximizing the integrated economic, social and environmental values and strive to be an excellent corporate citizen. Our dedication to customer satisfaction is reflected in everything we do, from our product design to our customer support. Our company believes that quality is the foundation of enterprise survival. We serve friends from all walks of life with low price, excellent quality and fast speed!
Post Insulators 16kN With Top And Bottom Flange.
Detailed Description
|
Rated Voltage: |
72.5kV |
SCL: |
16kN |
|
Type: |
Station Post |
Type Test: |
Provide |
|
Material: |
Composite, Polymer |
Sample Available: |
Yes |
Reasonable Design and Excellent material
|
End Fittings |
Core |
Sheds and Housing |
|
Materials: Hot dip galvanized cast iron or cast steel |
Epoxy & Glass Fiber |
HTV Silicone Rubber |
|
Min. thickness of the galvanization: 86μm |
Rod Diameter: Φ70mm |
Color: Gray,Red |

Technical Data
|
Rated Voltage |
Height |
Dry Arcing Distance |
Creepage Distance |
Specified Cantilever Load |
Max. Design Cantilever Load |
Max. Design Torsion Load |
Dry Power Frequency Withstand Voltage |
Lightning Impulse Withstand Voltage |
|
72.5 |
770±1 |
682mm |
1813 |
16kN |
10kN |
1.2kN • m |
165 |
325 |
Post Insulators Inspection and Testing
1.1Type Tests
The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.
(i)Verification of the dimensions
(ii)Mechanical failing load
(iii)Thermal-mechanical performance test
(iv)Dry lightning impulse withstand voltage test
(v)Wet Power-frequency withstand voltage test
1.2Routine Tests
The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.
(i)Routine visual inspection
(ii)Routine mechanical test
(iii)Routine electrical test
1.3Acceptance Tests
(i)Verification of the dimensions
(ii)Mechanical failing load test

Marking
Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.
Package and Transportation
Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.
We pursue the management tenet of 'Quality is remarkable, Company is supreme, Name is first', and will sincerely create and share success with all clientele for Composite Insulators Polymer Silicone Rubber Station Post Insulator. Newly introduced manufacturing equipment, a strong R&D team, a brand-new scientific management system and a professional after-sales service team have enhanced the influence of our company. Our company keeps promises and operates in compliance.
Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, polymer pin insulator, 138kV Composite Deadend Insulators, 66kV Composite Long Rod Insulator, post insulator and pin insulator, Polymer Post insulator for electrified railway, insulator line post