Fzsw-10/4 10kv Station Post Composite Insulator, Post Insulator

Fzsw-10/4 10kv Station Post Composite Insulator, Post Insulator

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

Product Introduction

We follow the direction of international popular development, follow the relevant international and national industry standards, high starting point, to provide users with 35kV Composite Deadend insulators, 138kV station post insulator, Composite Suspension Insulators For Railway that is in line with the development trend. Our company values efficiency and effectiveness in all aspects of our operations. The company insists on taking the struggling as the foundation, advocating the spirit of striving, and at the same time strives for every employee to realize themselves and get full growth on the platform provided by the company. We advocate the cultivation of a team of talented people, to play the human resources team scale effect. Our company adheres to the "serious, responsible and meticulous" work style, and we adopt advanced, scientific working methods and procedures to serve customers wholeheartedly.

Post Insulators 16kN With Top And Bottom Flange.

Detailed Description

Rated Voltage:

72.5kV

SCL:

16kN

Type:

Station Post

Type Test:

Provide

Material:

Composite, Polymer

Sample Available:

Yes

 

Reasonable Design and Excellent material

 

End Fittings

Core

Sheds and Housing

Materials: Hot dip galvanized cast iron or cast steel

Epoxy & Glass Fiber

HTV Silicone Rubber

Min. thickness of the galvanization: 86μm

Rod Diameter: Φ70mm

Color: Gray,Red

station post insulators

 Technical Data

Rated Voltage
(kV)

Height
(mm)

Dry Arcing Distance
(mm)

Creepage Distance
(mm)

Specified Cantilever Load
(SCL)

Max. Design Cantilever Load
(MDCL)

Max. Design Torsion Load
(MDTol)

Dry Power Frequency Withstand Voltage
(kV)

Lightning Impulse Withstand Voltage
(kV)

72.5

770±1

682mm

1813

16kN

10kN

1.2kN • m

165

325

 

Post Insulators Inspection and Testing

1.1Type Tests

The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.

(i)Verification of the dimensions

(ii)Mechanical failing load

(iii)Thermal-mechanical performance test

(iv)Dry lightning impulse withstand voltage test

(v)Wet Power-frequency withstand voltage test

 

1.2Routine Tests

The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.

(i)Routine visual inspection

(ii)Routine mechanical test

(iii)Routine electrical test

 

1.3Acceptance Tests

(i)Verification of the dimensions

(ii)Mechanical failing load test

 

 

tes

Marking

Each Post Insulators unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.

 

Package and Transportation

Insulator units shall be packed in plywood cases or solid wood cases. The packing shall afford adequate protection for the insulators during handling and shipping. We can provide CO(Original Certificates) if client need.

Contact now

 

 

 

Meanwhile, our company staffs a team of experts devoted to the development of Fzsw-10/4 10kv Station Post Composite Insulator, Post Insulator. We integrate the gene of innovation into the blood of our own development, so that every step we move forward is beating the pulse of innovation. We strive to bring customers newer, more creative and more valuable products, and strive to become a leading enterprise trusted and respected by the society.

Hot Tags: 72.5kV,16kN Post Insulators with Top and Bottom Flange 72.5kV, China, manufacturers, suppliers, factory, wholesale, for sale, Polymer stay insulator for guy wire, Spare Parts For Composite Insulators, 25kV Composite Deadend insulators, 66kV Composite Long Rod Insulator, Composite Braced Line post Insulator, 33kv post insulator

Send Inquiry

whatsapp

teams

E-mail

Inquiry